Single Gang Switch Box - 12 AWG
Number of 14 AWG wires: 0; Number of 12 AWG wires: 3; Number of 10 AWG wires: 0; Number of devices (switches, receptacles): 1; Number of internal cable clamps: 1; Number of ground wires: 1
Volume for ground wires: 0 cubic inches; Volume for clamps: 0 cubic inches; Volume for devices: 2 cubic inches; Volume of 10 AWG wires: 0 cubic inches; Volume of 12 AWG wires: 6.75 cubic inches; Volume of 14 AWG wires: 0 cubic inches; Total Minimum Volume Required: 8.75 cubic inches
Single Gang Receptacle Box - 12 AWG
Number of 14 AWG wires: 0; Number of 12 AWG wires: 4; Number of 10 AWG wires: 0; Number of devices (switches, receptacles): 1; Number of internal cable clamps: 1; Number of ground wires: 1
Volume for ground wires: 0 cubic inches; Volume for clamps: 0 cubic inches; Volume for devices: 2 cubic inches; Volume of 10 AWG wires: 0 cubic inches; Volume of 12 AWG wires: 9 cubic inches; Volume of 14 AWG wires: 0 cubic inches; Total Minimum Volume Required: 11 cubic inches
Two Gang Switch Box - 12 AWG
Number of 14 AWG wires: 0; Number of 12 AWG wires: 6; Number of 10 AWG wires: 0; Number of devices (switches, receptacles): 2; Number of internal cable clamps: 2; Number of ground wires: 2
Volume for ground wires: 0 cubic inches; Volume for clamps: 0 cubic inches; Volume for devices: 4 cubic inches; Volume of 10 AWG wires: 0 cubic inches; Volume of 12 AWG wires: 13.5 cubic inches; Volume of 14 AWG wires: 0 cubic inches; Total Minimum Volume Required: 17.5 cubic inches